Backflow assembly test: 4812 Fox Run Ct
ApprovedFiled Nov 15, 2026 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 15, 2026
- Assembly type
- RP
- Serial number
- A365377
- Size
- 3/4
- Test gauge serial
- G-5199
- Gauge calibration date
- May 29, 2026
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-62-01318
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4812 Fox Run Ct
Owner: Emerson Pruitt
Parcel 013-62-01318