Back to the backflow review queue
Backflow assembly test: Main Street Brewing Co
ApprovedFiled Jun 26, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 26, 2025
- Assembly type
- RP
- Serial number
- Z450606
- Size
- 2
- Test gauge serial
- G-7885
- Gauge calibration date
- Apr 26, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-48-01106
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9897 Laurel Ct
Owner: Whitcomb Holdings LLC
Parcel 005-48-01106