Backflow assembly test: 2943 Quarry Dr

Approved

Filed Aug 6, 2026 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 6, 2026
Assembly type
PVB
Serial number
K476990
Size
3/4
Test gauge serial
G-5498
Gauge calibration date
Dec 12, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Okafor, current on the service date
  • All required fields present
  • Address matches parcel 005-77-01355
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2943 Quarry Dr
Owner: Emerson Fairley
Parcel 005-77-01355