Back to the backflow review queue

Backflow assembly test: 3700 Turkey Hill Ln

Approved

Filed Nov 12, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 12, 2025
Assembly type
RP
Serial number
Z350881
Size
3/4
Test gauge serial
G-9521
Gauge calibration date
Mar 22, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-98-01227
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3700 Turkey Hill Ln
Owner: Quinn Ashby
Parcel 005-98-01227