Backflow assembly test: 7547 Laurel Trl

Approved

Filed May 7, 2026 by Hayden Stroud, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 7, 2026
Assembly type
RP
Serial number
W817734
Size
3/4
Test gauge serial
G-8001
Gauge calibration date
Jul 11, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-60-01132
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.