Backflow assembly test: Main Street Diner
ApprovedFiled Sep 12, 2025 by Drew Stroud, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 12, 2025
- Assembly type
- RP
- Serial number
- K927199
- Size
- 1
- Test gauge serial
- G-6084
- Gauge calibration date
- Jan 3, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 005-31-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6223 Hickory Trl
Owner: Lindqvist Holdings LLC
Parcel 005-31-01335