Back to the backflow review queue
Backflow assembly test: 2994 Old Church Ct
ApprovedFiled Jun 26, 2026 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 26, 2026
- Assembly type
- DC
- Serial number
- W966747
- Size
- 3/4
- Test gauge serial
- G-8143
- Gauge calibration date
- Dec 18, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Stroud, current on the service date
- All required fields present
- Address matches parcel 005-61-01028
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2994 Old Church Ct
Owner: Logan Ashby
Parcel 005-61-01028