Backflow assembly test: Main Street Apartments
ApprovedFiled Aug 11, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 11, 2025
- Assembly type
- RP
- Serial number
- B407138
- Size
- 1 1/2
- Test gauge serial
- G-5778
- Gauge calibration date
- Jan 30, 2025
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-19-01116
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.