Back to the backflow review queue

Backflow assembly test: 8300 Sycamore Ln

Approved

Filed Jan 11, 2026 by Morgan Marsh, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 11, 2026
Assembly type
DC
Serial number
A111059
Size
1
Test gauge serial
G-3031
Gauge calibration date
Aug 15, 2025
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 073-97-01235
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8300 Sycamore Ln
Owner: Morgan Hollins
Parcel 073-97-01235