Backflow assembly test: 7409 Hickory Dr

Approved

Filed Mar 26, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 26, 2025
Assembly type
PVB
Serial number
K908716
Size
3/4
Test gauge serial
G-1816
Gauge calibration date
Oct 31, 2024
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-50-01328
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.