Back to the backflow review queue

Backflow assembly test: 5804 Quarry Way

Approved

Filed Jul 19, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 19, 2024
Assembly type
RP
Serial number
Z239396
Size
1
Test gauge serial
G-2247
Gauge calibration date
Jan 25, 2024
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-74-01258
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5804 Quarry Way
Owner: Avery Kessler
Parcel 073-74-01258