Back to the backflow review queue

Backflow assembly test: 5852 Orchard Dr

Approved

Filed Apr 3, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 3, 2025
Assembly type
RP
Serial number
A401853
Size
3/4
Test gauge serial
G-8881
Gauge calibration date
Oct 10, 2024
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-40-01013
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5852 Orchard Dr
Owner: Alex Ashby
Parcel 073-40-01013