Backflow assembly test: 6411 Pine Knoll Rd
Needs reviewFiled Nov 27, 2026 by Drew Harlow, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 27, 2026
- Assembly type
- RP
- Serial number
- B463652
- Size
- 3/4
- Test gauge serial
- G-5845
- Gauge calibration date
- Feb 4, 2026
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Harlow, current on the service date
- All required fields present
- Address matches parcel 073-75-01337
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6411 Pine Knoll Rd
Owner: Taylor Nguyen
Parcel 073-75-01337