Backflow assembly test: 7950 Spring Branch Ln
ApprovedFiled May 6, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 6, 2024
- Assembly type
- PVB
- Serial number
- B354579
- Size
- 3/4
- Test gauge serial
- G-7200
- Gauge calibration date
- Sep 22, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Whitcomb, current on the service date
- All required fields present
- Address matches parcel 073-16-01229
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7950 Spring Branch Ln
Owner: Drew Harlow
Parcel 073-16-01229