Back to the backflow review queue
Backflow assembly test: 3002 Turkey Hill Rd
ApprovedFiled Nov 10, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 10, 2025
- Assembly type
- RP
- Serial number
- Z198584
- Size
- 3/4
- Test gauge serial
- G-5456
- Gauge calibration date
- May 9, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Whitcomb, current on the service date
- All required fields present
- Address matches parcel 073-39-01025
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3002 Turkey Hill Rd
Owner: Casey Okafor
Parcel 073-39-01025