Backflow assembly test: 3974 Pine Knoll Ln
Needs reviewFiled Nov 18, 2026 by Drew Harlow, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 18, 2026
- Assembly type
- DC
- Serial number
- B962158
- Size
- 1
- Test gauge serial
- G-1781
- Gauge calibration date
- Apr 22, 2026
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Harlow, current on the service date
- All required fields present
- Address matches parcel 073-36-01232
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
3974 Pine Knoll Ln
Owner: Cameron Brandt
Parcel 073-36-01232