Backflow assembly test: Golden Animal Hospital
ApprovedFiled Apr 14, 2026 by Drew Harlow, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 14, 2026
- Assembly type
- RP
- Serial number
- B728330
- Size
- 4
- Test gauge serial
- G-1499
- Gauge calibration date
- May 27, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Harlow, current on the service date
- All required fields present
- Address matches parcel 073-66-01297
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.