Backflow assembly test: 8052 Meadow Lark Rd
ApprovedFiled Oct 21, 2023 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 21, 2023
- Assembly type
- PVB
- Serial number
- A562299
- Size
- 3/4
- Test gauge serial
- G-2317
- Gauge calibration date
- Jun 29, 2022
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 073-39-01225
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8052 Meadow Lark Rd
Owner: Reese Lindqvist
Parcel 073-39-01225